Place of use
These cable are used to electronic control systems connection, voice frequency transmission, signal and communication cables Halogen free cables have flame retardant properties and low smoke density.
| Inner Conductor | Electrolytic Stranded Annealed Copper Wire, Class 5 |
| Insulation | HFFR Compound EN 50290-2-26, DIN 47100 Colour Code |
| Individual Screen | PES Tape, Tinned Copper Wire Braiding |
| Individual Sheath | HFFR Compound EN 50290-2-27, RAL 7001 Grey |
| Stranding | Screened and Sheated Pairs Stranded In Layers |
| Seperator | PES Tape |
| Screen | Tinned Copper Wire Braiding |
| Outer Sheath | HFFR Compound EN 50290-2-27, RAL 7001 Grey |
| Product Code | Dimension and Weights | Electrical Properties | |||||||||
| Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
| In Ground at 20° C | On Air at 30° C | ||||||||||
| CONDUCTOR | INSULATION | CAPACITANCE | CURRENT CARRYING | OPERATING | TEST | BENDING | TEMPERATURE | ||||||||
| mm² | Ω/km | MΩxKm | mm² | pf/m | mm² | A | 300/500 V | 1500V | 7,5XD | -30ºC +70ºC | |||||
| 0.22 | 88 | ≥ 200 | 0.22 | 110 | 0.22 | 2.5 | |||||||||
| 0.34 | 56 | 0.34 | 110 | 0.34 | 4.5 | ||||||||||
| 0.50 | 39 | 0.50 | 120 | 0.50 | 6 | ||||||||||
| 0.75 | 26 | 0.75 | 120 | 0.75 | 13 | ||||||||||
| 1.00 | 19.5 | 1.00 | 130 | 1.00 | 16 | ||||||||||
| 1.50 | 13.3 | 1.50 | 140 | 1.50 | 20 | ||||||||||
| 2.50 | 7.98 | 2.50 | 150 | 2.50 | 25 | ||||||||||
| FLAME RETARDANT TEST | SMOKE DENSITY TEST | TEST ON CORROSIVENESS | HALOGEN | FLAME | |||||||||||
| IEC 60332-1-2 VDE 0482-332-1-2 EN 60332-1-2 | IEC 61034-2 | IEC 60754-2 VDE 0482-267-2-3 EN 50267-2-3 | IEC 60754-1 VDE 0482-267-2-1 EN 50267-2-1 | IEC 60332-3-24 VDE 0482-332-3-24 EN 60332-3-24 | |||||||||||
| |||||||||||||||